TECH IMPRO AUTOMATION SOLUTION SDN BHD
7263, 1st Floor, Lorong Chempa, 12200 Butterworth, Penang, Malaysia.
+6012-466 1514

eYc DPT02 Signal Converter

Previous 9 / 11 Next

eYc DPT02 Signal Converter Signal / Meter / Instrumentation eYc
Quantity
Add Quotation


Features:Local display, easy keypad programming the signal output and scale, led for working status.
Accuracy : 0.2%F.S.±1 digital
Sampling time : 4 cycle / sec
Response time adjustment range : 0.5 ... 60 sec
Input & Output : Voltage 0...5 V / 0...10 V ; Current 0...20 mA / 4...20 mA
Output signal : Analog output / Relay / RS-485

Description

Local display, easy keypad programming the signal output and scale, led for working status.
● Measuring input type:DC Current / DC Voltage 
● More output type:Analog output / RS-485 / Relay / 2 Channel output 
● 20-Point linear calibration
● Signal isolation:Power supply / Analog input / Analog output / RS-485
● Power supply:AC 85 ... 253 V;Auxiliary supply output(DC 16 ... 25 V / 23 mA), use for 2-wire & 3-wire transmitter
● User-friendly. high light red LED display panel, 7.6 mm(height of character), 3 digits, -199 ... 999, 7-segment display
● DIN rail installation, high safety & stability, fire-proof case, moisture-proof cover
● Field : Chemical industry / Energy / Water circulation system / Oil & gas / Marine / Factory automation / Metal & steel / Cement / Pulp & paper / Pharmaceuticals / Food & beverage

Specification

Display readout:3 Digits(-199 ... + 999) / Decimal point : 0 ... 2 Place, button
Display:Highlight red LED(7-segment) 
Digit height7.6 mm
Accuracy0.2%F.S.±1 digital
Sampling time:4 cycle / sec
Response time adjustment range:0.5 ... 60 sec
Input : Voltage:0 ... 5 V;0 ... 10 V;Current : 0 ... 20 mA;4 ... 20 mA 
Output : Voltage:0 ... 5 V;0 ... 10 V;Current : 0 ... 20 mA;4 ... 20 mA 
Output signal : Analog output  / Relay / RS-485
Load resistance : Current : RL<500 Ω;Voltage≧10 KΩ
Analogue output resolution : 16 bit
Signal error detection : Yes

Relays
Alarm hysteresis:Display value or 0 ... 100%
ON and OFF delay:0 ... 3600 sec
Output signal error detection:Yes     
Relay actuation direction:Upper limit:HI, AL;Lower limit:LO, AL

Communication / Electrical
Protocol:RS-485 Modbus RTU, master or slave
RS-485 baud rate:9600, 19200, 38400, 57600, 115200 bps
Operating environment:-10 ...  +60°C;0 ... 95%(Non-condensing)
Storage environment:-25 ...  +70°C
Power supply:AC 85 ... 253 V
Auxiliary power:DC 16 .. 25 V / 23 mA
Insulation voltage endurance:2 KVac / 1 min 
Parameter memory type:Flash
Dissipated power:5 W
Isolation:Power supply / Analog input / Analog output / RS-485
IP rating:IP20
Electrical protection : ■ Polarity protection ■ Over-voltage
Certification:CE
Housing:ABS fire-proof class(UL94V-0)
Dimensions(HxWxD):99.5 x 25.5 x 104.2 mm
Weight : About 158 g

Application

Chemical Industry / Energy / Oil & gas / Marine /Water circulation system / Factory automation /Metal & steel / Cement / Pulp & paper /Pharmaceuticals / Food & beverage

Please leave your enquiry here, we will reply as soon as possible.
Name*  
Company Name  
Product Interested  
Quantity  
Email*  
Contact No.*  
Attachment  
*only support gif, jpeg, jpg, png, pdf
Messages*  

You have 0 items in you cart. Would you like to checkout now?
0 items