TECH IMPRO AUTOMATION SOLUTION SDN BHD
7263, 1st Floor, Lorong Chempa, 12200 Butterworth, Penang, Malaysia.
+6012-466 1514

eYc FTS140 Hot Wire Air Velocity Transmitter

Previous 5 / 10 Next

eYc FTS140 Hot Wire Air Velocity Transmitter Air Velocity Transmitter Flow / Air Velocity / Air Volume eYc
Quantity
Add Quotation


Features:Using Mass flow principle A better choice for HVAC engineering
Measuring range:0 ... 20 m/s
Minimum measuring range:0.2 m/s
Signal:4 ... 20 mA / DC 0 ... 10 V
Accuracy(+25°C):±3%F.S.
●YUDEN-TECH CO.,LTD. Calibration Laboratory - ( ILAC / TAF ) Test report, for more detailed information please contact us.
(TAF accreditation:3032, complying with ISO / IEC 17025 ) TAF has mutual recognition arrangement with ILAC MRA

Description

Using Mass flow principle A better choice for HVAC engineering

● Hot wire mass flow transmitter
● IP rating:IP54
● Linear adjustment function
● Switching analog output by dip switch
● Off set function by button
● The housing and probe material are PC fire-proof

FTS140 hot wire air velocity transmitter, using mass flow measuring principle, stable electrical bridge with good accuracy, simple structure, stable performance and low flow sensitivity.
It is suitable for use in HVAC air conditioning environment measurement, optimization and adjustment of system performance, ventilation control.
Duct type, easy installation, suitable is used extensively in environmental engineering projects, as facility and factory maintenance.

Specification

Sensor:Hot wire mass flow transmitter
Measuring range:0 ... 20 m/s
Minimum measuring range:0.2 m/s
Signal:4 ... 20 mA / DC 0 ... 10 V
Signal connection:3-wire
Load resistance:Current output:≦500 Ω / Voltage output:≧10 KΩ
Reaction time:t90≦5 sec(τ:90%)
Installation angle effect:<3% of the measured value(When the installation angle<10°)
Accuracy(+25°C):±3%F.S.(Nonlinear error, Hysteresis error, Repeatability error )
Temp. effect:0.3% / °C
Medium & Temp.:Air;0 ... 50°C
Body operating Temp.:0 ... 50°C
Body operating Humid.:95%RH(Non-condensing)
Storage Temp.:-20 ... +60°C
Power supply:DC 24 V & AC 12 ... 30 V
Current consumption:DC 24 V:120 mA / AC 12 V:350 mA, AV 24 V:180 mA
Overvoltage protection:DC:<40 V / AC:<40 V
Electrical connections:Terminal
Installation:Duct type / Flange type
IP rating:IP54
Electrical protection:■ Polarity protection ■ Over-voltage ■ Short-circuit
Certification:CE
Material:PC
Weight:~150 g

Application

Monitoring air and flow for industrial process / HVAC / Building / Factory